RXM3AB2FD
ActivePOWER RELAY, 3PDT, 110 VDC, 10 A, ZELIO RXM SERIES, SOCKET
Deep-Dive with AI
Search across all available documentation for this part.

RXM3AB2FD
ActivePOWER RELAY, 3PDT, 110 VDC, 10 A, ZELIO RXM SERIES, SOCKET
Deep-Dive with AI
Technical Specifications
Parameters and characteristics for this part
| Specification | RXM3AB2FD |
|---|---|
| Approval Agency | CE, IECEE, Lloyd's, GOST, UL, CSA |
| Coil Current | 8.2 mA |
| Coil Resistance | 13.44 kOhms |
| Coil Type | Non Latching |
| Coil Voltage | 110 VDC |
| Contact Form | 3PDT (3 Form C) |
| Contact Material | Silver Nickel (AgNi) |
| Contact Rating (Current) | 10 A |
| Features | Test Button, Lighted Indicator |
| Load - Max Switching | 2500 VA, 280 W |
| Mounting Type | Socketable |
| Must Operate Voltage | 88 VDC |
| Must Release Voltage | 11 VDC |
| Operate Time | 20 ms |
| Operating Temperature [Max] | 55 °C |
| Operating Temperature [Min] | -40 °C |
| Relay Type | General Purpose |
| Release Time | 20 ms |
| Switching Voltage | 250 VAC, 28 VDC |
| Termination Style | Plug In |
RXM3A Series
| Part | Coil Current | Release Time | Mounting Type | Approval Agency | Contact Material | Operate Time | Features | Coil Resistance | Termination Style | Relay Type | Coil Type | Switching Voltage | Load - Max Switching | Must Release Voltage | Contact Rating (Current) | Contact Form | Must Operate Voltage | Coil Voltage | Operating Temperature [Min] | Operating Temperature [Max] |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
SQUARE D BY SCHNEIDER ELECTRIC | 67.6 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Lighted Indicator Test Button | 710 Ohms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 280 W 2500 VA | 7.2 VAC | 10 A | 3PDT (3 Form C) | 38.4 VAC | 48 VAC/DC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 67.6 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Test Button | 710 Ohms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 280 W 2500 VA | 7.2 VAC | 10 A | 3PDT (3 Form C) | 38.4 VAC | 48 VAC/DC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 75 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Lighted Indicator Test Button | 160 Ohms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 280 W 2500 VA | 1.2 VDC | 10 A | 3PDT (3 Form C) | 9.6 VDC | 12 VDC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 133.3 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Lighted Indicator Test Button | 180 Ohms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 187.6 W 1675 VA | 3.6 VAC | 6.7 A | 3PDT (3 Form C) | 19.2 VAC | 24 VAC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 36.9 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Lighted Indicator Test Button | 650 Ohms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 187.6 W 1675 VA | 2.4 VDC | 6.7 A | 3PDT (3 Form C) | 19.2 VDC | 24 VDC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 75 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Test Button | 160 Ohms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 280 W 2500 VA | 1.2 VDC | 10 A | 3PDT (3 Form C) | 9.6 VDC | 12 VDC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 8.2 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Test Button | 13.44 kOhms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 280 W 2500 VA | 11 VDC | 10 A | 3PDT (3 Form C) | 88 VDC | 110 VDC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 8.2 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Lighted Indicator Test Button | 13.44 kOhms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 280 W 2500 VA | 11 VDC | 10 A | 3PDT (3 Form C) | 88 VDC | 110 VDC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 15.3 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Test Button | 15 kOhms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 280 W 2500 VA | 34.5 VAC | 10 A | 3PDT (3 Form C) | 184 VAC | 230 VAC | -40 °C | 55 °C |
SQUARE D BY SCHNEIDER ELECTRIC | 27.1 mA | 20 ms | Socketable | CE CSA GOST IECEE Lloyd's UL | Silver Nickel (AgNi) | 20 ms | Lighted Indicator | 4.43 kOhms | Plug In | General Purpose | Non Latching | 28 VDC 250 VAC | 187.6 W 1675 VA | 18 VAC | 6.7 A | 3PDT (3 Form C) | 96 VAC | 120 VAC | -40 °C | 55 °C |
Pricing
Prices provided here are for design reference only. For realtime values and availability, please visit the distributors directly
Description
General part information
RXM3A Series
Harmony RXM miniature plug-in relay has a coil control voltage of 110VDC and has 3 changeover contacts 3PDT (triple pole double throw) with a rating of 10A. It has large choice of number of contacts for high rated current use with space-saving design. It also offers one-step lockable test button and LED for readiness. It helps to reduce the size of enclosures and increase machine reliability, you can mount nearly everywhere. The product is IP40 and has a transparent cover allowing operator to visually inspect the status of contacts. Workability for hard-wired logic automated systems to complement the functions of industrial programmable logic controllers (PLCs). Status display with LED, clearly signal both in the day and night. RXM Relay should be used with a RXZE socket (screw clamp, screw connector, push-in terminal). To protect against vibrations, plastic/metal clamp can be added to the socket.
Documents